CIX6500 System
|
Features
|
Data-Linc Group designed the wireless Communication Interface Extender (CIX) System specifically to offer a cost effective, industrial grade automation I/O extender that provides direct PLC connection via communication ports to I/O points— no complicated PLC programming or proprietary software. The easy-to-implement CIX utilizes Data-Linc’s proprietary, field-proven SRM wireless technology. The updated CIX products offer new internal logics that will extend product longevity and future support. They also feature a faster processor, increased security with AES-256 encryption and provide greater firmware capacity for increasing features going forward without the need to purchase new units, dovetailing well with Data-Linc’s commitment to backward compatibility for the corresponding legacy versions. These industrial grade wireless products offer simplified, low-labor startup, maintenance and growth for I/O in both the 900 MHz (CIX643x) and the 2.4 GHz (CIX653x) ISM license-free bands. Wired Remote expansion is also available (CIX/EXR).
The Communication Interface Extender system goes beyond standard I/O devices. The “head end” is a dual port CIX6535 Master with an Ethernet and serial port for connection to a PC or PLC. The Ethernet interface supports EtherNet/IP or Modbus TCP/IP and the serial interface supporting full duplex DF1 or Modbus RTU protocols. The CIX6535 communicates wirelessly with up to 16 CIX6530 Remote I/O units to form a single wireless I/O network for seamless protocol integration into your equipment. Protocol communications with the CIX Master is as documented by the equipment manufacturer to utilize Data-Linc’s point addressing model.
Each CIX6530 Remote provides 8 discrete inputs, 8 discrete outputs, 4 analog inputs and 4 analog outputs. A full network with 16 CIX Remotes provides a total of 384 I/O points. Discrete inputs are self-sensing dry contact. Discrete outputs are open collector common emitter (sinking), and the 12 bit resolution analogs can be configured for 0-20ma, 4-20ma and 0-10VDC.
Wireless communication is based on Data-Lincs robust and proprietary SRM Smart SpectrumTM FHSS technology. All SRM radio features are available including Repeater, Remote and Repeater/Remote modes. Operation of two or more CIX wireless networks in near proximity and in the same ISM band is supported. LincViewTM OPC real time wireless RF network diagnostics is also supported. The result is extremely robust and reliable I/O communication for both in-plant or in-the-field use (range up to 10 miles with line of sight), even in high noise environments. The CIX system has excellent noise immunity, but should loss of wireless communication occur, each output point can be forced to a specified value or to hold last value, and the communications loss is indicated by a status light and an output bit for event notification. Using Network ID mode permits replacement of any CIX unit without reconfiguring any other CIX unit. All I/O connections are via pluggable terminal blocks to simply initial wiring, and if required, a CIX unit can be replaced without the need to rewire. Each CIX Remote can be wire connected to CIX/EXP expansion unit Remote via RS232 or RS485 wiring. This permits I/O point expansion at or near a CIX location.
Field configuration of each CIX unit is straight forward using Data-Linc’s configuration software. CIX wireless I/O is also backed by Data-Linc Groups extensive background and knowledge of PLC’s and was specifically designed for PLC communications.
The CIX wireless I/O network is ideal for data acquisition and control applications. The Communication Interface Extender is an excellent option for installations looking toward future growth. Merely add another Remote or another CIX network. Whether an installation is small and requires only a few discrete points or is expanding to multiple networks of discrete and analog I/O, the CIX wireless I/O system can meet the challenge and provide cost-effective reliable solution. It is also ARRA compliant.
* American Recovery and Reinvestment Act of 2009
Download pdf (934K) the printable version of the Data Sheet for the CIX6500 System Communication Interface I/O Extender. (Requires Adobe Acrobat Reader to open.)
^ Top of Page ^
Operating Frequency
License-free, 2.4 GHz ISM band
Included
CD. Configuration Software, LincViewTM OPC RF Network Management Software, User Manual, Quick Start
Antenna. Test Antenna
0 dB bench test anten
Power Supply
Operating ranges
System gain. 129 dB
Distance. 10 miles (16 km) LOS with omni antennas
Transmitter
RF Output Power. 500 mW maximum, 27 dB (programmable steps)
Modulation. Frequency Hopping Spread Spectrum, GFSK
Hop Patterns. 15 (user selectable)
Occupied Bandwidth. 230KHz
Error Correction. 32 bit CRC
RF Encryption. Substitution Dynamic Key, up to 256 bit AES encryption
Receiver
Sensitivity. -105 dBm @ 115.2kbps for BER 10-4
-102 dBm @153.6kbps 10-4 for BER
Selectivity. 40 dB @ fc ±230 KHz and 60dB @ fc ±460 KHz
Operating Environment
Temperature. -40° to 167° F (-40° to 75° C)
Humidity. 0 to 95% non-condensing
Enclosure. 18 gauge steel
Standard. 18-gauge steel
2.47 X 3.70 X 6.4 in. (6.274 X 9.398 X 16.26 cm)
Optional. DIN rail mounting flanges (included)
Shipping Weight. 1.8 lb (0.82 kg)
Included 7' Cat 5 Cable
Connections
Antenna. Standard thread female SMA for optional external omni directional or yagi antennas
external omni directional or yagi antennas.
Ethernet. 10/100 Base-T Auto-MDIX
Diagnostic port. RS232 DB9 Female or RS485-2-wire
Power 3-pin pluggable terminal block
Indicators
LAN. Link/Act
RF.Power (P), RF Carrier (C), RF Output (O), RF Input (I)
Mode. M1, M2, L1, L2
Power
Voltage. 10-28 VDC nominal
Current. 160mA idle, 660mA peak on transmit
Operating Environment
Temperature. -40 to 167°F (-40 to 75°C)
Humidity. 0 to 95% non-condensing
Channel Functions
Analog. 0-20 mA, 4-20mA or 0-10 VDC, 24VDC
max. loop voltage, 12 bit resolution. Self-powered outputs.
Discrete Input. Dry contact closure
Discrete Output. Open collector (sink to ground), 100mA per channel, 12-24VDC
Connections
Antenna. Standard thread female SMA for optional external omni directional or yagi antennas
I/O Discrete and Analog. Detachable screw-type terminal blocks Wire size 12-26 AWG
Power. 3-pin pluggable terminal block
Diagnostic port. Standard DB9 Female
EX-Linc. RS232 DB9 Female or RS485 2-wire
Indicators
General. Power (P), RF Carrier (C), RF Input (I),
RF Output (O), and Comm Error
Discrete. Activity LED for each discrete I/O
Power
Voltage. 12-28 VDC nominal
Current. 160 mA idle, 660mA peak on transmit
^ Top of Page ^
^ Top of Page ^ | ||
|
||
Products |
Features & Benefits | Focus Item | Product Selection Guides | Catalog | PDF Library | Order Information | |
Tech Resources |
Engineering Specifications | Articles & Technical Papers | Installation Information | |
Partners |
GE Fanuc | Omron | Rockwell Automation | Schneider Electric | Siemens | Technology Partners | |
Industries |
Security | Traffic | and other industry application notes and diagrams | |
Sales Channels |
Distributors | System Integrators | OEMs | |
News |
Tradeshows and Events | Press Releases | Newsletters | |
About Us |
Overview | Jobs/Employment | Office Locations/Contact Information | |
ChineseEspañol | ||
|
||
© 1996-2015 Data-Linc Group. All rights reserved. |
140129 |